Home
Safety
Qualified and authorised staff
Residual risks
Personal protective equipment
Safety references
General safety references
Technical documents to be additionally observed
Requirements for connection cables
Check regularly
How to get to the CM-RC-02 info website
Required tools and specifications for the connection cables
Remove existing compressor protection device (SE-B*)
Installing CM-RC-02 in protection mode
Schematic wiring protection mode
Installing CM-RC-02 in
compressor operation mode
Schematic wiring compressor operation mode
Add-on kits CM-RC-02
Oil heater
Discharge gas temperature sensor
Oil monitoring
Closing module housing and laying cables
Before commissioning, check tightness
Extension board CM-IO-B
Add-on kits CM-IO-B
Pressure transmitters
High pressure transmitter
Low pressure transmitter
Refrigerant injection (RI)
Oil monitoring OLM-IQ
Solenoid valve and solenoid valve for capacity control
Additional fan
Closing module housing and lay cables
Before commissioning, check tightness
Connecting CM-RC-02 to the
BEST SOFTWARE
Download the BEST SOFTWARE
Connect BEST interface converter to CM-RC-02
Connect CM-RC-02 via Bluetooth
Configuring CM-RC-02 with the
BEST SOFTWARE
Activating protection mode (SE-B* mode)
Activating the oil heater
Overheat protection - activating the discharge gas temperature sensor (PT1000)
Activating oil monitoring
Activating compressor operation mode
Activating an extension board
Activating CRII compressor capacity regulation (VARISTEP)
Refrigerating capacity control: Setting evaporating temperature
Activating system control mode
Activating system operating mode
Downloading a device log
-------------------------------
PERFORMANCE KITS
ENERGY KIT
Remove existing compressor protection device (SE-B*)
Installing CM-RC-02 in system control mode
Extension board CM-IO-B
Discharge gas temperature sensor
Pressure transmitters
High pressure transmitter
Low pressure transmitter
Capacity control
Dismantle cylinder head
Mount and connect cylinder head and solenoid valve for capacity control
Closing module housing and lay cables
Before commissioning, check tightness
Connect and configure ENERGY KIT with the BEST SOFTWARE
Activating an extension board
Activating system control mode
Refrigerating capacity control: Setting evaporating temperature
Activating CRII compressor capacity regulation (VARISTEP)
Overheat protection - activating the discharge gas temperature sensor (PT1000)
Activating system operating mode
SAFETY KIT
Remove existing compressor protection device (SE-B*)
Installing CM-RC-02 in
compressor operation mode
Oil heater
Discharge gas temperature sensor
Oil monitoring
Closing module housing and lay cables
Before commissioning, check tightness
Connect and configure SAFETY KIT with the BEST SOFTWARE
Activating compressor operation mode
Activating the oil heater
Overheat protection - activating the discharge gas temperature sensor (PT1000)
Activating oil monitoring
CONNECTIVITY KIT
Remove existing compressor protection device (SE-B*)
Installing CM-RC-02 in
compressor operation mode
Connect and configure the CONNECTIVITY KIT with the BEST SOFTWARE
Activating compressor operation mode
-------------------------------
Electrical connection
Representation of components and cables
Legend and schematic wiring diagrams
Connecting the protective earth conductors