Low pressure transmitter
Remove sealing plug and clean thread
- Rags and cloths
- 13 mm socket wrench
Mount screw-in nipple
- 13 mm socket spanner
- Torque spanner
- Tightening torque: 20 Nm
Mounting the low pressure transmitter
- Spanner SW16 (counterhold with spanner SW 13)
- Torque spanner
- Tightening torque: 15 Nm
Plug in low-pressure transmitter cable
Connect cable cores to terminal strip CN27
- Slotted screwdriver
Terminal strip CN27, terminal 1: BLACK: "+5V Sup."
Terminal strip CN27, terminal 2: BROWN: "Signal"
Terminal strip CN27, terminal 3: RED: "GND"
Close the cable glands at the end.