Oil monitoring

If subsequently mounting the prism unit of the oil monitoring:

Risk of refrigerant loss! Check the thread. Carefully screw the new component in and tighten it to the prescribed tightening torque. Perform a tightness test before commissioning!

Risk of refrigerant loss!

Check the thread.

Carefully screw the new component in and tighten it to the prescribed tightening torque.

Perform a tightness test before commissioning!

Remove screw and metal gasket from bearing cover

Clean threaded hole

Screw in and mount prism unit with new metal gasket

If subsequently mounting the prism unit of the oil monitoring:

Risk of refrigerant loss! Check the thread. Carefully screw the new component in and tighten it to the prescribed tightening torque. Perform a tightness test before commissioning!

Risk of refrigerant loss!

Check the thread.

Carefully screw the new component in and tighten it to the prescribed tightening torque.

Perform a tightness test before commissioning!

Mounting the opto-electronic unit

Risk of compressor failure!

Risk of compressor failure!

Possible failure of the protection device due to penetrating moisture!

Ensure that the cable connection always faces down!

Connect cable cores to terminal strip CN4

Terminal strip CN4, terminal 1: GREY: "Signal"

Terminal strip CN4, terminal 2: RED: "GND"

Terminal strip CN4, terminal 3: BLUE: "+24V Sup."

Terminal strip CN4, terminal 4: BROWN: "GND"

Close the cable glands at the end.