Solenoid valve and solenoid valve for capacity control

In order to mount the solenoid valves forcapacity control as described below, it is required that the respective cylinder heads for capacity control are pre-mounted on the compressor.

In order to mount the solenoid valves forcapacity control as described below, it is required that the respective cylinder heads for capacity control are pre-mounted on the compressor.

For further information, please refer to the following technical information:

Remove blind flanges and gaskets

Clean the sealing surfaces, fit a new seal and mount the solenoid valve

Fit new seal and pay attention to the position of the guide pins!

Mount the solenoid valve with new screws!

Attach the seals of the electric connector of the device

Screw the electric connector of the device to the solenoid coils

Put the solenoid coil onto the solenoid valve

Connect cable cores "CR1" to terminal strip CN20 and screw the protective conductor to the earthing terminal strip

Terminal strip CN20, terminal 7: BROWN: "D04"

Terminal strip CN20, terminal 8: BLUE: "N"

 

Connect protective earth conductor to earthing terminal strip

Connect cable cores "CR2" to terminal strip CN21 and screw the protective conductor to the earthing terminal strip

Terminal strip CN21, terminal 1: BROWN: "D05"

Terminal strip CN21, terminal 2: BLUE: "N"

 

Connect protective earth conductor to earthing terminal strip

Close the cable glands at the end.