Remove existing compressor protection device (SE-B*)
WARNINGRisk of electric shock!

Risk of electric shock!
Before working on the terminal box, module housing and electrical lines: Switch off the main switch and secure it against being switched on again!
Close the terminal box and the module housing before switching on again!
Authorized staff
All work done on the products and the systems in which they are or will be installed may only be performed by qualified and authorised staff who have been trained and instructed in all work. The qualification and competence of the qualified staff must correspond to the local regulations and guidelines.
Remove cover of terminal box
- Cross head screwdriver size 2
Unscrew power voltage supply and safety chain from the existing compressor protection device
- Cross head screwdriver size 2
Unscrew the protective earth conductor from the earthing terminal strip
- Cross head screwdriver size 2
Pull out the cable, close and seal the cable bushing
Remove clamp type cable lugs of motor temperature monitoring from terminal plate
- Needle nose pliers
Remove compressor protection device from the terminal box
Press spring clips slightly to the side
- Needle nose pliers