ECO connections

Most screw compressors are equipped with an additional suction gas connection for operation with economiser (ECO) as standard. Various adapters, e.g. with shut-off valves, are available as options.

For the first order, the compressors are supplied with the standard (sealing screw / blind flange) specified here. If one of the options is required, this must be specified when ordering - preferably with the designation in the following table. Details of the components can be found in the subordinate chapters (see below, also linked from the table).

HS.53 .. 85 and OS.53 .. 85 compressors have a combined ECO / LI connection.

HS.53 .. 85 and OS.53 .. 85 compressors have a combined ECO / LI connection.

A compressor can therefore only be used with ECO or with LI, not with both at the same time.

Nominal diameters (DN) are not actual dimensions!

Nominal diameters (DN) are not actual dimensions!

The nominal diameters DN10 .. DN200 only indicate ranges! The number is not a quantifiable unit, it is only indirectly related to the diameters of the connections and should not be used in calculations.

Economiser connections of Bitzer screw compressors
*: Not available for all types, as the largest motors may not be suitable for ECO operation. The Bitzer Software shows for each compressor model if the option is available.
–: No spare part assembly available. When reordering in ePARTS, check which individual parts are needed in each case.

Compressor

ECO connection standard

ECO connection options

Option as spare part (part no. assembly), see also: spare part assemblies

HS.53 .. 74

Sealing screw M26x1,5

Valve D22L–7/8''–DN20

361 330 01

Bush DN20 (1 1/4'')

361 331 02

Connection piece D22–7/8''

–

HS.85

Blind flange

Valve D28L–1 1/8''–DN25

361 330 12
Mounting instructions

HS.95

Sealing screw M48x1,5

Valve D35L–1 3/8''–DN36 (2 1/4'')

361 330 26

Bush D42L–1 5/8''–DN40

361 330 23

Valve D42L–1 5/8''–DN40

361 330 22

OS.53

Sealing screw M22x1,5

Valve D22L–7/8''–DN20

361 330 02

Bush D16L–1 1/4''–DN15

–

Connection piece D22–7/8''

–

OS.74

Sealing screw M26x1,5

Valve D22L–7/8''–DN20

361 330 01

Bush DN20 (1 1/4'')

–

Connection piece D22–7/8''

–

OS.85

Blind flange

Valve D28L–1 1/8''–DN25

361 330 09
Mounting instructions

Connection piece D28–1 1/8''

–

OS.A53

Sealing screw M22x1,5

Valve with bush DN20 (1 1/4'')

361 369 10

Bush D16L–1 1/4''–DN15

–

OS.A74

Sealing screw M26x1,5

Valve with bush DN20 (1 1/4'')

361 369 10

Bush DN20 (1 1/4'')

–

OS.A85

Blind flange

Valve with bush DN32 (1 3/4'')

361 330 13

Bush DN32 (1 3/4'')

361 330 18

OS.A95

Sealing screw M48x1,5

Valve with bush DN40

361 330 19

Bush DN40 (2 1/4")

361 330 20

Valve with bush DN32 (2 1/4'')

361 330 24

Bush DN32 (2 1/4'')

361 330 25

OS.A105

Blind flange DN80

Welding flange DN80

Adaptor and valve DN80

CSH(P)65 .. 75

Sealing screw M22x1,5

Valve D22–7/8'' with pulsation muffler

361 329 16

CSH76

Sealing screw M26x1,5

Valve D22L–7/8''–DN20

361 330 03

CSH(P)85

Blind flange

Valve D28L–1 1/8''–DN25

361 330 05
Mounting instructions

CSH86

Sealing screw M26x1,5

Valve D28L–1 1/8''–DN25

361 330 15

CSH(P)95
CSH2T95

Blind flange

Valve D35L–1 3/8''–DN36 (1 3/4'')

361 330 07

CSH96

Sealing screw M26x1,5

Valve D35L–1 3/8''–DN36 (1 3/4'')

361 330 16

CSW65

Sealing screw M22x1,5

Valve D22L–7/8''–DN20*

361 330 01

CSW75

Sealing screw M26x1,5

Valve D22L–7/8''–DN20*

361 330 03

CSW85

Sealing screw M26x1,5

Valve D28L–1 1/8''–DN25*

361 330 15

CSW95

Sealing screw M26x1,5

Valve D35L–1 3/8''–DN36 (1 3/4'')*

361 330 16

CSW105

Sealing screw M48x1,5

Valve with bush DN40

361 330 19

CSV.2

Sealing screw M26x1,5

Valve D22L–7/8''–DN20 with pulsation muffler

361 330 17
Mounting instructions CSVH

CSV.3

Sealing screw M26x1,5

Valve D28L–1 1/8''–DN25 with pulsation muffler

361 330 21
Mounting instructions CSVH

Valves with the same designation are not necessarily interchangeable!

Valves with the same designation are not necessarily interchangeable!

The above table sometimes contains links to the same valves, but they are supplied in different assemblies. Valves with the same designation are therefore not necessarily interchangeable. When ordering, it is thus necessary to specify for which compressor the valve is to be used.

For further information on the position of the connections on the compressor, pipe layout and ECO operation, see Technical Information ST-610. In addition, the respective operating instructions for the compressor must be observed.