Available mechanical capacity control

For capacity control in combination with the CM-RC-02 compressor module, extension board A (CM-IO-A) or B (CM-IO-B) is always required.

For capacity control in combination with the CM-RC-02 compressor module, extension board A (CM-IO-A) or B (CM-IO-B) is always required.

Ordering a compressor with capacity control but without an extension board therefore only makes sense if

The maximum number of capacity regulators per compressor also depends on the compressor model (Connection positions of the capacity regulators).

Reciprocating compressors for R744 (CO2)

Overview mechanical capacity control for semi-hermetic BITZER reciprocating compressors for R744 (CO2), subject to change.
CR: stepped capacity control,
CRII: virtually stepless capacity control.

Compressor

Mechanical capacity control optionally available?

CM-RC-02 with extension board CM-IO-A or CM-IO-B

Protection device SE-B* or CM-RC-02 without extension board
(only stepped capacity control, external controller necessary)

ECOLINE compressors for R744, transcritical applications

2MTE .. 2KTE

(on request)

4PTE(M) .. 4KTE(M)
4JTE(M) .. 4CTE(M)
6FTE(M) .. 6CTE(M)

yes

CRII cylinder head and solenoid valve mounted and wired

CR cylinder head mounted, solenoid valve enclosed

4PTE(M)U .. 4KTE(M)U
4JTE(M)U .. 4CTE(M)U
6FTE(M)U .. 6CTE(M)U

yes

CRII cylinder head and solenoid valve mounted and wired

CR cylinder head mounted, solenoid valve enclosed

8FTE .. 8CTE

yes

CR cylinder head and solenoid valve mounted and wired
(CM-RC-02 + CM-IO-B is standard scope of delivery)

--

ECOLINE compressors for R744, subcritical applications

2NSL .. 4NSL

--

2MME .. 8PME

--

Semi-hermetic reciprocating compressors for hydrocarbons (HC), HFC, HFO

Overview mechanical capacity control for semi-hermetic BITZER reciprocating compressors for hydrocarbons, HFC, HFO, subject to change.
CR: stepped capacity control,
CRII: virtually stepless capacity control.

Compressor

Mechanical capacity control optionally available?

CM-RC-02 with extension board CM-IO-A or CM-IO-B

Protection device SE-B* or CM-RC-02 without extension board
(only stepped capacity control, external controller necessary)

ECOLINE PRO compressors for hydrocarbons (HC)

2KESP .. 2FESP

2KESP.X3 .. 2FESP.X3

--

2EESP .. 8FEP

yes

CRII cylinder head and solenoid valve mounted and wired

Options:

  • CR cylinder head and solenoid valve mounted
  • CR cylinder head prepared, without solenoid valve

2EESP.X3 .. 8FEP.X3

yes

CRII cylinder head and solenoid valve mounted and wired

--

2KESP.EX .. 2FESP.EX

2KESP.X2 .. 2FESP.X2

--

2EESP.EX .. 8FEP.EX

2EESP.X2 .. 8FEP.X2

yes

--

CR cylinder head mounted (without IQ MODULE)

ECOLINE compressors for HFC / HFO

2KES .. 2FES

--

2EES(H) .. 2CES(H)
4FES(H) .. 4FE(H)
6JE(H) .. 6FE(H)
8GE .. 8FE

Tandem compressors accordingly

yes

CRII cylinder head and solenoid valve mounted and wired

Options:

  • CR cylinder head mounted, solenoid valve enclosed
  • CR cylinder head prepared, without solenoid valve

2KES.EX .. 2FES.EX

--

2EES.EX .. 2CES.EX
4FE.EX .. 4FE.EX
6JE.EX .. 6FE.EX
8GE.EX .. 8FE.EX

yes

--

CR cylinder head mounted (without IQ MODULE)

Special models

4Z-5.2 .. 4N-20.2

yes

--

Options (without IQ MODULE):

  • CR cylinder head pre-mounted, solenoid valve enclosed
  • CR cylinder head prepared, without solenoid valve

For condensing units, essentially the same options are available as for the compressors they contain; see price list and BITZER SOFTWARE.

Open drive reciprocating compressors

Overview mechanical capacity control for BITZER open drive reciprocating compressors, subject to change.

Compressor

Mechanical capacity control (always without IQ MODULE)

Open drive compressors for R717

W2TA .. W2NA

--

W4TA .. W4GA
W6HA .. W6FA

Options:

  • CR cylinder head pre-mounted, solenoid valve enclosed
  • CR cylinder head prepared, without solenoid valve

Open drive compressors for HFC / HFO

2T.2 .. 2N.2

--

4T.2 .. 4G.2
6H.2 .. 6F.2

Options:

  • CR cylinder head pre-mounted, solenoid valve enclosed
  • CR cylinder head prepared, without solenoid valve

The mounting of the enclosed solenoid valve with a pre-mounted cylinder head is described in the chapter on retrofitting (Pre-mounted cylinder head: Mounting the solenoid valve).

In many cases, existing compressors can be retrofitted with mechanical capacity control, but this requires replacing the cylinder heads (Retrofitting capacity regulators).