Introduction and overview
Bitzer offers various couplings and fitting coupling housings as accessories for OS. compressors. Both can be selected in the BITZER Software together with the compressor. Mounting the coupling using the coupling housing simplifies the correct alignment of compressor and motor. For special designs (e.g. booster systems), special coupling housings are available on request.
In general, only couplings with elastic intermediate elements that can compensate for small displacements in the axial direction and do not themselves exert any axial force may be used. All Bitzer couplings meet these requirements. They are installed e.g. as shown in the following illustrations.
The following table shows which Bitzer couplings and coupling housings are available for which compressors. The respective designation contains a link to the detailed description.
OS(A)53 | OS(A)74 | OS(A)74EX | OS(A)85 | OS.A95 | OS.A105 | |
|---|---|---|---|---|---|---|
Couplings | ||||||
|
Bore for motor shaft: D42 (also 1 5/8''), D48 (also 1 7/8''), D55, D60 or pre-drilled D20 | X | |||||
|
Bore for motor shaft: D48, D55, D60 or pre-drilled D20 | X | |||||
|
Bore for motor shaft: 1 7/8'', D55, D60, D65 or pre-drilled D20 | X | |||||
|
Bore for motor shaft: D75 or pre-drilled D20 | X | |||||
|
Bore for motor shaft: D48, D55, D60 or pre-drilled D20 | X | |||||
|
Bore for motor shaft: 1 7/8'', D55, D60, D65 or pre-drilled D20 | X | |||||
|
Bore for motor shaft: D75 or pre-drilled D20 | X | |||||
|
Bore for motor shaft: D55, D60, D65, D70 or pre-drilled D20 | X | |||||
|
Bore for motor shaft: D55, D60, D65, D70, D75, D80 or pre-drilled D20 with various hub lengths on the motor side | X | |||||
|
Bore for motor shaft: D70, D75, D80 or pre-drilled D40 with various hub lengths on the motor side | X | |||||
Coupling housings | ||||||
|
Motor flange D350 | X | |||||
|
Motor flange D400 | X | |||||
|
Motor flange D400 | X | X | ||||
|
Motor flange D450 | X | X | ||||
|
Motor flange D450 | X | X | X | X | ||
|
Motor flange D550 | X | X | X | X | ||
|
Motor flange D660 | X | X | X | X | X | |
|
Motor flange D800 | X | X | ||||
|
Motor flange D1000 | X | |||||
|
Motor flange D1150 | X | |||||
For OS.A95 and OS.A105, a coupling with split halves (without coupling housing) will also be available in the future.
Also observe the following technical documents:
- SB-500: Operating instructions Open drive screw compressors OS.53 .. 74
- SB-509: Operating instructions Open drive screw compressors in special explosion-proof design
- SB-520: Operating instructions Open drive screw compressors OS.85, OS.95, OS.105
- SW-501: Replacement of the shaft seal OS.85 (video)
- SW-502: Replacement of the shaft seal OS.95 (video)
- SW-110: Inspection and replacement intervals with semi-hermetic and open drive screw compressors
- AW-100: Tightening torques for screwed connections