Mounting OLM-IQ-AS (B43 and M41)

The OLM-IQ is delivered pre-assembled and fully electrically connected if ordered with the compressor. The OLM-IQ-AS is mounted in place of the sight glass, if it is retrofitted. The oil level in the compressor is in the sight glass range.

  1. Position the compressor at an angle before dismantling the sight glass.
  2. For compressors that have already been assembled: Drain the oil or have an oil pan ready. Replenish this oil after assembly.
  3. According to the type of oil, prevent air from entering the compressor and do not reuse drained oil.
Damage to the compressor caused by degraded refrigeration compressor oil.

Damage to the compressor caused by degraded refrigeration compressor oil.

Moisture is chemically bound to the synthetic oil and cannot be removed by evacuation.

Proceed with extreme care:

Any penetration of air into the system and oil drum must be avoided under all circumstances.

Use only oil drums in their original unopened state!

This applies to all oils that are not mineral oils, e. g. polyolester oil (POE oil), polyalkylene glycol oil (PAG oil) and polyvinyl ether oil (PVE oil).

Retrofitting differs depending on the sight glass.

Tightening torques see leaflet AW-100 or Mind when mounting or replacing.

Mounting in place of a sight glass with sealing flange

Mounting of OLM-IQ-AS that replaces a sight glass with sealing flange
Mounting of OLM-IQ-AS that replaces a sight glass with sealing flange
  1. Remove sight glass and gasket.
  2. Check and clean threads.
  3. Check all sealing surfaces of components and clean if necessary.
  4. Place O-ring (3) in sight glass (2).
  5. Place O-rings (5) and (7) in adaptor flange (6).
  6. Orientate the adaptor flange according to the illustration: Place the side with the five holes directly onto the compressor housing. Align the marking on the front ring to the right.
  7. Fix adaptor flange with actuator sensor unit (4) and sight glass (2).
  8. Align the actuator sensor unit exactly horizontally when the compressor is mounted. Angular deviation of the top edge from the horizontal: maximum 1°.
  9. Tighten the screws (1) in several steps.

Mounting in place of a screwed sight glass

Mounting of OLM-IQ-AS that replaces a screwed sight glass
Mounting of OLM-IQ-AS that replaces a screwed sight glass
  1. Remove sight glass and gasket.
  2. Check and clean threads.
  3. Check all sealing surfaces of components and clean if necessary.
  4. Place O-ring (5) in screw adaptor (6).
  5. Place adapter ring (7) and seal (8) over screw adaptor.
  6. Screw in screw adaptor.
  7. Fix actuator sensor unit (4) with O-ring (3) and sight glass (2). Align the marking of the adaptor ring to the right.
  8. Align the actuator sensor unit exactly horizontally when the compressor is mounted. Angular deviation of the top edge from the horizontal: maximum 1°.
  9. Tighten the screws (1) in several steps.