Mind when mounting or replacing
WARNINGThe compressor is under pressure!

The compressor is under pressure!
Serious injuries are possible.
Depressurise the compressor!
Wear safety goggles!
Assess the risk of intervention and take appropriate measures, for example: Wear additional personal protective equipment, shut off system or shut off the valves before and after the respective system part and depressurise.
The use of original spare parts is understood to be covered by the type test. The quality of these components has been verified.
The following chapters may contain information for products that are not described in this manual.
Before mounting
- Clean thread and threaded bore carefully.
- Use new gaskets only!
- Flat gaskets and O-rings may be moistened slightly with oil.
- Do not oil gaskets with metallic support!
- Only use the gasket provided in each case.
- When making modifications to a R744 compressor cylinder head, use new screws only.
Admissible screwing methods
- Tighten with calibratable torque spanner to indicated torque.
- Tighten with pneumatic impact wrench and retighten with calibratable torque spanner to indicated torque.
- Tighten with calibratable electronically controlled angled wrench to indicated torque.
- Test tightening torque by turning further.
- Tolerance: ±6% of the nominal value applies if only one value is listed.
- Torque ranges apply without tolerance.
Flange connections
- Tighten them crosswise and in at least 2 steps (50/100%).