Connecting the application limits monitoring to the CM-RC-01
Compressors for standard refrigerants
NOTICE
Incorrect measurement data leads to compressor failure.
Incorrect measurement data leads to compressor failure.
Do not interchange high and low pressure transmitters. Check the marking on the screwed nipple exactly.
- Connect the cables of the two pressure transmitters on the CM-RC-01 to terminal strip CN12 according to the schematic wiring diagrams.
- High pressure transmitter B50: to terminals 1, 2 and 3. That is the screwed sensor with marking "HP" or "2CP5-71-47".
- Low pressure transmitter B51: to terminals 4, 5 and 6. That is the screwed sensor with marking "LP" or "2CP5-71-49".
Compressors for R744 applications
NOTICE
Incorrect measurement data leads to compressor failure.
Incorrect measurement data leads to compressor failure.
Do not interchange the cables of high and low pressure transmitters.
- Connect the cables of the two pressure transmitters on the CM-RC-01 to terminal strip CN12 according to the schematic wiring diagrams.
- High pressure transmitter B50: to terminals 1, 2 and 3. This screwed sensor is mounted on the compressor to connection position 1a (HP).
- Low pressure transmitter B51: to terminals 4, 5 and 6. This screwed sensor is mounted on the compressor to connection position 3a (LP).
The measurement data of the pressure transmitters are logged as soon as the cables are connected, namely as dew point values of evaporation and condensing temperature. However, application limits monitoring must be selected, Activating application limits monitoring.