Prerequisite: High and low pressure transmitters must be installed.
Set the refrigerant in the best software: In the menu Configuration, window Main Setup, select the refrigerant used.
In the menu Configuration, window Protection functions, row Enable application envelope protection in the column User Setting, enter Yes.
The programmed application limits cannot be adjusted. However, the permissible range can be restricted via high and low pressure cut-out. See next subchapter.