Demount old frequency inverter

Authorized staff

All work done on the products and the systems in which they are or will be installed may only be performed by qualified and authorised staff who have been trained and instructed in all work. The qualification and competence of the qualified staff must correspond to the local regulations and guidelines.

De-energize compressor

Before carrying out any work in the FI housing, switch off the main switch. This also applies if the compressor has been switched off either by the function "Safe Torque Off" (STO) or "Motor Off". The FI still remains energized!

Life-threatening voltages inside the FI housing!
danger

Life-threatening voltages inside the FI housing!

Contact can lead to serious injuries or death.

Never open the FI housing in operation!

Switch off the main switch and secure it against being switched on again.

Wait for at least 5 minutes until all capacitors have been discharged!

Before switching on again, close the FI housing.

Remove housing cover of the frequency inverter

Ensure that terminal CN1 (supply for peripheral devices) is de-energized

Ensure that mains phases L1, L2, L3 are de-energized

Ensure there is no voltage between the conductor rails and earth screws

Mark terminals at control board

Remove terminals from control board

Label terminals at extension board

Remove terminals CN16, CN18 and CN19 from terminal board

Ensure there is no voltage between the conductor rails and earth screws

Unplug cable of pressure transmitter

Remove cable cores of temperature sensor from terminal CN8

Remove cable cores from temperature sensor and terminal CN19 from extension board

Unscrew and remove cable of evaporator pressure valve and coil

Remove all demounted cables and components

Demount electronic expansion valve and evaporator pressure valve

Demount flange of the electronic cooling unit valve group

Remove terminals CN14, CN15 and CN8 from extension board

Unscrew/Unplug protective earth conductor and terminals CN2 .. CN9

Remove protective earth conductor and terminals CN2 .. CN9 as well as terminal CN17

Remove conductor rails

Remove plug of motor temperature sensors

Secure frequency inverter with lifting device

Demount frequency inverter

Lift and remove frequency inverter (FI)

Lift the frequency inverter slowly. Press firmly against lower part of housing.

Lift the frequency inverter slowly. Press firmly against lower part of housing.