Oils for hydrocarbon refrigerants (R290, R600a, etc.)

Characterising the oils

Bitzer oils for hydrocarbon refrigerants in screw compressors

Oil

Oil type

Applications

Designation on compressor

B-PAG220

polyalkylene glycol oil (PAG)

standard oil charge for CSHP

"Z" (e.g. CSHP7553-70Z)

SHC230

poly-alpha-olefin oil (PAO)

permitted for CSHP in existing systems

"P" (e.g. CSHP7553-70P)

SHC228

poly-alpha-olefin oil (PAO)

standard for HSNP with refrigerants R1270

only on request: HSNP with refrigerant R290

(HS. compressors are supplied without oil charge and therefore do not show the relevant dsignation.)

Material safety data sheets

Apart from this document, please observe the material safety data sheet (MSDS) for the respective oil. It contains information on toxicity, handling, personal protective equipment and disposal of the oil. Material safety data sheets for all Bitzer oils are available on request.

Application range

Risk of explosion and thus danger of death in the event of refrigerant outlet and in the presence of an ignition source!

Risk of explosion and thus danger of death in the event of refrigerant outlet and in the presence of an ignition source!

Refrigerant can ignite and also form an explosive atmosphere depending on its concentration in air!

Avoid open fire and ignition sources in the machinery room and in the hazardous zone!

Owing to the particularly high solubility of refrigerants of safety group A3 (e.g. R290, propane) in customary oils, BITZER compressors are charged with a special oil of a high viscosity index and particularly good tribological characteristics.

In view of the solubility, the design, operating mode and control of the compressor and the system are subject to particular requirements. Low or insufficient superheat in operation and insufficient heating of the oil in the compressor or oil separator during shut-off periods lead to a substantial reduction of the oil viscosity in the compressor. This results in reduced performance, heavy wear on drive gear parts, increased oil carry over and foaming. Secure compressor against ''wet operation'' and ensure sufficiently high suction gas superheat. The discharge gas temperature of reciprocating compressors must be at least 20 K, of compact screw compressors at least 30 K above the condensing temperature in summer and winter operation.

For further information on the use of R290 in semi-hermetic compressors:

Technical data

Overview of the technical data of BITZER refrigeration compressor oils.
The density can be linearly interpolated between the specified values.

Oil

Type

Flash-point (°C)

Pour point (°C)

Density (g/ml)

Kinematic viscosity (cSt)

Specific heat capacity (kJ/kg*K)

Thermal conductivity (W/m*K)

at -30°C

at 15°C

at 100°C

at 20°C

at 40°C

at 100°C

at 40°C

at 100°C

at 40°C

at 100°C

B-PAG220

PAG

240

-42

1.031

0.997

0.934

626

223

37.5

1.84

2.06

0.15

0.15

SHC230

PAO

260

-39

0.85

220

25

SHC228

PAO

255

-45

0.84

97

13.7

Miscibility gaps

Miscibility gaps for R290: Limit temperature depending on oil content (mass % of oil in oil refrigerant blend).
M: Range of complete miscibility.

Refrigerant solubility in oil

The following diagram can be used to read off the refrigerant content in the lubricant depending on refrigerant pressure and oil temperature.

Oil for R290: Refrigerant pressure depending on the oil temperature and the refrigerant content (mass % of refrigerant in oil-refrigerant blend).

Warning values for used oils

The listed oils are categorized as group KE according to DIN51503-1. To determine the used condition of the oil, e.g. with respect to water content or total acid number (TAN), the reference values of DIN 51503-2, apply.

Warning values for used Bitzer oils for hydrocarbon refrigerants.
(*): that is ± 15% of the value for new oil

Oil

Kinematic viscosity at 40°C (DIN EN ISO3104)

Max. water content
(DIN51777)

Total acid number
(DIN ISO6618)

B-PAG220

outside of 189 .. 256 cSt (*)

800 mg H2O/‍kg oil

0.2 mg KOH/‍g

SHC230

outside of 187 .. 253 cSt (*)

80 mg H2O/‍kg oil

0.2 mg KOH/‍g

SHC228

outside of 83 .. 111 cSt (*)

80 mg H2O/‍kg oil

0.2 mg KOH/‍g

In case of maintenance, be sure to observe the following:

Danger of spark formation due to unintended switching operations or overheating of the oil heater during oil change.

Danger of spark formation due to unintended switching operations or overheating of the oil heater during oil change.

Prior to interventions in the refrigerant circuit, interrupt the power supply on the main switch!

Observe special regulations for storage and transport of flammable gases.

When performing maintenance work indoors, always switch on room ventilation!

Danger of spark formation, when discharging electrostatic charges!

Danger of spark formation, when discharging electrostatic charges!

Take measures against electrostatic charging of non-metallic components, tools, auxiliaries and clothing! For example: Wear suitable antistatic clothing, use spark-free tools. If necessary, perform additional earthing of conducting parts.

Fire hazard!

Fire hazard!

The used oil contains a relatively large amount of dissolved refrigerant.

Pack used oil safely. Dispose of in an environmentally friendly manner.

  1. Hydrocarbons, for example propane, R290 or propene, R1270 and low-fluorinated flammable refrigerants, for example R1234yf, dissolve very well in refrigeration compressor oil at room temperature. This also applies to blends containing these substances.
  2. Used oil from such systems may still contain relatively high percentages of dissolved flammable gases even at atmospheric pressure. These components gas out.
  3. Observe during storage and transport:
  1. Fill used oil into pressure resistant vessels.
  2. Fill vessels with nitrogen as a protective gas and close them.
  3. Mark them, e. g. with the warning sign "flammable substance" W021 from ISO7010.

Elastomer compatibility

Relevant literature recommends the following seaI materials for polyalkylene glycol oils (PAG) and poly-alpha-olefin oils (PAO) with hydrocarbon refrigerants: