Connecting cables
Connect the compressor module electrically according to the schematic wiring diagrams. Observe safety standards EN60204-1, IEC60364 and national safety regulations.
WARNING
Risk of electric shock!
Before working on the terminal box, module housing and electrical lines: Switch off the main switch and secure it against being switched on again!
Close the terminal box and the module housing before switching on again!
The compressor module may be damaged or fail!
Never apply any voltage to the terminals of CN7 to CN12 – not even for test purposes!
The voltage applied to the terminals of CN13 must not exceed 10 V!
The voltage applied to terminal 3 of CN14 must not exceed 24 V! Do no apply voltage to the other terminals!
Never apply voltage to the voltage outputs, not even for testing.
Tightening torques see leaflet AW-100 or Mind when mounting or replacing.