Module is mounted in terminal box

The photo shows an example.

Installation situation: The compressor module is mounted in the terminal box. The protective conductor cable and the two cables for motor temperature monitoring are connected directly to the compressor module.

  1. Remove the terminal box cover.
  2. Lead the power cables for the compressor motor through suitable cable bushings into the terminal box.
  3. Connect the power cables according to the label on the inside of the terminal box cover. Observe the operating instructions of the compressor.
  4. Seal the cable bushings well.
  5. Check the protective conductor cable and the two cables for the motor temperature monitoring.
  6. Check all cable connections on the terminal plate for a tight fit.
  7. Close the terminal box and screw on the cover.