Compressors for R744
- High pressure transmitter B50 for transcritical R744 applications
- marking: HP
- thread: 3/8-24 UNF
- connection position 1a (HP)
- High pressure transmitter B50 for subcritical R744 applications with high standstill pressures
- marking: LP
- thread: 1/2-20 UNF
- connection position 1a (HP)
- Because of the pressure levels, the pressure transmitter with marking LP and thread 1/2-20 UNF is also used on high pressure side with these compressors.
- Low pressure transmitter B51
- marking: LP
- thread: 1/2-20 UNF
- connection position 3a (LP)
Connection position see Operating Instructions KB-130, chapter Mounting, connections, positions 1a (HP) und 3a (LP) or Dimensional drawings.
Mounting pressure transmitters
- Remove plugs from position 1a (HP) and 3a (LP).
- Check the threads.
- Put on the copper seal.
- Screw pressure transmitters.
Tightening torques see leaflet AW-100 or Mind when mounting or replacing.