Compressors for standard refrigerants
- High pressure transmitter B50
- marking: HP or 2CP5-71-47
- thread: 1/8-27 NPTF
- connection position 1 (HP)
If the high pressure switch is planned at this position, then both components are mounted here via a T-piece. - Low pressure transmitter B51
- marking: LP or 2CP5-71-49
- thread: 1/8-27 NPTF
- connection position 3 (LP)
Connection position see Operating Instructions KB-104, chapter Mounting, Connections, positions 1 (HP) and 3 (LP) or Dimensional drawings.
Tightening torques see leaflet AW-100 or Mind when mounting or replacing.
Mounting the high pressure transmitter
- Remove plug from position 1 (HP).
- Check the thread.
- Mount a T-piece with 1/8-27 NPTF threads.
- Connect the high pressure transmitter and the high pressure switch to the T-piece.
- Alternatively, the high pressure transmitter can also be connected to the liquid line directly after the receiver.
Mounting the low pressure transmitter
- Remove plug from position 3 (LP).
- Check the thread.
- Screw low pressure transmitter.
- Or if a low pressure switch is to be connected: Mount a T-piece with 1/8-27 NPTF threads at this position and connect the low pressure transmitter and the low pressure switch to it.