Installing the RI system
The RI system consists of
- 1 RI injection valve with electric connector of the device and cable to CM-RC-01
- 1 RI injection nozzle for 4-cylinder compressors
- 2 RI-injection nozzles with connecting line for 6-cylinder compressors
- Operation via the CM-RC-01
The RI system can also be retrofitted.
Tightening torques see leaflet AW-100 or Mind when mounting or replacing.
Required tools
- open ring spanner
- torque spanner
Installing the RI system
- Remove plugs at the injection point(s). 1 plug for 4-cylinder compressors and 2 plugs for 6-cylinder compressors. For the position(s), see the operating instructions, chapter Mounting, Connections, position(s) 4 (CIC).
- Install the RI injection nozzle(s).
- Remove the union nut and sealing cap from all RI injectors.
- For 4-cylinder compressors: Screw the RI injection valve onto the RI injection nozzle. Orient the pipe inlet in the opposite direction of the plenum box. Tighten the screws at the end of the connecting line, holding them against the RI injection nozzle.
For 6-cylinder compressors: Screw the ends of the fork-shaped connecting line onto one RI injection nozzle each. Tighten the screws at the ends of the connecting line, holding them against the RI injection nozzle. Orient the pipe inlet parallel to the discharge gas line. - Fix the connecting line close to the valve with a clamp to avoid vibrations. To do this, screw on a fastening plate for the clamp under the next cylinder head screw.
- For 6-cylinder compressors: Attach a second mounting plate to the side cylinder head directly below the second bend of the longer part of the connecting line. Fasten the connecting cable here also with a clamp.