Retrofitting cylinder heads for capacity control

Capacity control can be retrofitted as a complete kit on the cylinder banks provided for this purpose. The capacity control kits, including part numbers and mounting instructions, are listed in the ePARTS Software for the respective compressor.

The installation of capacity control may necessitate additional cooling of the compressor! Observe the application limits (Application limits for part load operation)!

The installation of capacity control may necessitate additional cooling of the compressor! Observe the application limits (Application limits for part load operation)!

The standard cylinder head must be replaced with a cylinder head for capacity control. It can only be retrofitted as a complete kit.

The compressor is under pressure!
warning

The compressor is under pressure!

Serious injuries are possible.

Depressurise the compressor!

Wear safety goggles!

For tightening torques see

Incorrect installation can cause the cylinder head to burst!

Incorrect installation can cause the cylinder head to burst!

Before commissioning the converted compressor, carry out a strength pressure test / tightness test.