Remove existing compressor protection device (SE-E*)
WARNINGRisk of electric shock!

Risk of electric shock!
Before performing any work in the terminal box: Switch off the main switch and secure it against being switched on again!
Close the terminal box before switching on again!
Authorized staff
All work done on the products and the systems in which they are or will be installed may only be performed by qualified and authorised staff who have been trained and instructed in all work. The qualification and competence of the qualified staff must correspond to the local regulations and guidelines.
Remove cover of terminal box
- 5 mm hexagon spanner
Remove cable cores of discharge gas temperature sensor (PTC) from terminal 5 at terminal board
- Screwdriver
Remove cable cores of PTC resistors for monitoring the motor winding temperature from compressor protection device (SE-E*)
- Phillips screwdriver
Remove clamp type cable lugs for phase monitoring from motor bolts
- Pliers
Remove compressor protection device (SE-E*) from terminal box
- Phillips screwdriver