Controlling the compressor via Modbus
The compressor can be monitored and controlled via Modbus.
In case the compressor shall be controlled via Modbus, the parameter "Modbus control" must be set to "Modbus directly". If the gateway for the BITZER digital network (BDN, access via myBITZER) is connected between the system controller and the IQ module, "Modbus control" must be set to "Modbus via BDN Gateway". By default, "Modbus control" is set to "Deactivated", so that the compressor can be controlled via digital/analogue signals only.
When Modbus control is enabled, the setpoints from the different interfaces (analogue setpoint and serial setpoint) are merged and the resulting "Setpoint" can be read via the Modbus interface. The setpoint is limited to 100%, even if the sum of the setpoints may be above 100%.
Serial control word
The serial control word is set via the Modbus holding register 110:
Parameter | Unit | Data type | Scaling | Address (I/H) | Register count |
|---|---|---|---|---|---|
Serial control word | None | uint16 | 110(H) | 1 |
Bit definition of the serial control word:
Bit | Function | Description |
|---|---|---|
0 .. 2 | Reserved | Should be set to 1 (for compatibility to the CSV) |
3 | Enable operation | Must be set to 1 |
4 .. 5 | Reserved | Should be set to 1 (for compatibility to the CSV) |
6 | Start | Start command |
7 | Reset | Alarm reset command is active when bit is set from 0 to 1. |
8 .. 9 | Reserved | |
10 | Data valid | Must be set to 1 to instruct the controller to accept the serial control word.
The resulting control word (I102) will always have this bit set. |
11 .. 15 | Reserved |
Examples of serial control word setups:
Command | Hexadecimal value | Decimal value | Binary | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
Reserved | Data valid | Reserved | Reset | Start | Reserved | Enable operat. | Reserved | |||
No command / Stop | 43F | 1087 | 00000 | 1 | 00 | 0 | 0 | 11 | 1 | 111 |
Start | 47F | 1151 | 00000 | 1 | 00 | 0 | 1 | 11 | 1 | 111 |
Reset | 4BF | 1215 | 00000 | 1 | 00 | 1 | 0 | 11 | 1 | 111 |
The neutral value of the control word is 43F hex (= 1087 dec = 10000111111 binary).
To start the compressor, the control word must be 47F hex (= 1151 dec = 10001111111 binary).
Serial setpoint
The serial setpoint is set via the Modbus holding register 111:
Parameter | Unit | Data type | Scaling | Address (I/H) | Register count |
|---|---|---|---|---|---|
Serial setpoint | % | int16 | 100 | 111(H) | 1 |
Modbus control timeout function
If the Modbus communication is interrupted, the IQ module can be configured for different reactions to this interruption by the parameters "Modbus control timeout function" and "Modbus control timeout".
Configuration possibilities for the timeout function:
- None --> Do nothing (if compressor is running, operation will be continued)
- Stop --> Stop the compressor
- Fault --> Stop the compressor and trip with the fault alarm "11-00 Serial Control Timeout"
Any received Modbus telegram resets the timeout function.
Status word
The actual status of the IQ module can be seen via the Modbus input register 103.
Parameter | Unit | Data type | Scaling | Address (I/H) | Register count |
|---|---|---|---|---|---|
Status word | None | uint16 | 1 | 103(I) | 1 |
Status word bit definitions
Bit | Function | Description |
|---|---|---|
0 .. 1 | Not used | |
2 | Operation enabled | 0 = The compressor is not ready for operation
|
3 | Fault | 0 = No fault alarm(s) |
4 .. 6 | Not used | |
7 | Warning | 0 = No warning alarm(s) |
8 | On reference | 0 = The compressor is ramping or not running. |
9 .. 10 | Not used | |
11 | Running | 0 = Compressor is not running
|
12 | Start active | 0 = Compressor start is not active
|
13 | Critical | 0 = No critical alarm(s) |
14 .. 15 | Not used |