BITZER oils for refrigerants of safety class A1
NOTE
Retrofit of R22 to HFC blends: due to their high polarity, polyol ester oils (POE) must be used. Sufficient miscibility/solubility is not guaranteed when MO (mineral oil) and/or AB (alkylbenzene) lubricants are used!
Reciprocating compressors
Refrigerant | BITZER oil type |
|---|---|
R134a R404A, R407A/C/F, R448A, R449A, R449C R450A, R452A, R452C, R507A, R513A | BSE32 |
R134a (tc > 70°C) R410A | BSE55 |
R22 | B5.2 |
See also:
- KT-500: BITZER refrigeration compressor oils for reciprocating compressors
- BITZER SOFTWARE
Screw compressors
Verdichtertyp | Kältemittel | BITZER Ölsorte |
|---|---|---|
CSVH | R134a, R450A, R513A, ... | BSE170 |
CSVW | R134a, R450A, R513A, ... | BSE170L |
CSH65 .. CSH95, CSK61 | R134a, R407A/C/F, R450A, R513A, ... | BSE170 |
R22 | B320SH | |
CSH76 .. CSH96 | R134a, R450A, R513A, ... | BSE170L |
R134a, R450A, R513A, ...: tc < 60°C | BSE170 | |
CSW65 .. CSW95 | R134a, R407A/F, R450A, R513A, ... | BSE170L |
R22 | B320SH | |
R407C | BSE170 | |
CSW105 | R134a, R450A, R513A, ... | BSE170L |
OS.53 .. OS.85 | R134a, R404A, R407A/C/F, R507A, ... | BSE170 |
R22: to= -5°C .. -50°C, tc < 45°C | B100 | |
R22: to= +12.5°C .. -40°C, tc < 60°C | B150SH | |
HS.53 .. HS.95 | R134a, R404A, R407A/C/F, R507A, R448A, R449A, ... | BSE170 |
R22: to= -5°C .. -50°C, tc < 45°C | B100 | |
R22: to= +12.5°C .. -40°C, tc < 60°C | B150SH |
See also:
- ST-500: Bitzer refrigeration compressor oils for compact screw compressors CS., CSV.
- BITZER SOFTWARE