BITZER oils for refrigerants of safety class A1

NOTE

Retrofit of R22 to HFC blends: due to their high polarity, polyol ester oils (POE) must be used. Sufficient miscibility/solubility is not guaranteed when MO (mineral oil) and/or AB (alkylbenzene) lubricants are used!

Reciprocating compressors

BITZER oils for reciprocating compressors and refrigerants of the safety class A1

Refrigerant

BITZER oil type

R134a

R404A, R407A/C/F, R448A, R449A, R449C R450A, R452A, R452C, R507A, R513A

BSE32

R134a (tc > 70°C)

R410A

BSE55

R22

B5.2

See also:

Screw compressors

BITZER oils for screw compressors and refrigerants of the safety class A1

Verdichtertyp

Kältemittel

BITZER Ölsorte

CSVH

R134a, R450A, R513A, ...

BSE170

CSVW

R134a, R450A, R513A, ...

BSE170L

CSH65 .. CSH95, CSK61

R134a, R407A/C/F, R450A, R513A, ...

BSE170

R22

B320SH

CSH76 .. CSH96

R134a, R450A, R513A, ...

BSE170L

R134a, R450A, R513A, ...: tc < 60°C

BSE170

CSW65 .. CSW95

R134a, R407A/F, R450A, R513A, ...

BSE170L

R22

B320SH

R407C

BSE170

CSW105

R134a, R450A, R513A, ...

BSE170L

OS.53 .. OS.85

R134a, R404A, R407A/C/F, R507A, ...

BSE170

R22: to= -5°C .. -50°C, tc < 45°C

B100

R22: to= +12.5°C .. -40°C, tc < 60°C

B150SH

HS.53 .. HS.95

R134a, R404A, R407A/C/F, R507A, R448A, R449A, ...

BSE170

R22: to= -5°C .. -50°C, tc < 45°C

B100

R22: to= +12.5°C .. -40°C, tc < 60°C

B150SH

See also: