Substitutes for R22

For futher information and alternatives see BITZER Refrigerant Report.

The following table shows the data for R22 and alternative refrigerants.

ODP: ozone depletion potential
GWP: global warming potential according to EN 378:2017; AR4: Fourth Assessment Report of the IPCC, AR5: Fifth Assessment Report of the IPCC, AR6: Sixth Assessment Report of the IPCC
pract. limit AEL: assigned exposure limit according to EN 378:2017
Temperature glide: Total glide from bubble to dew line, based on 1.013 bar. Real glide depends on operating conditions.
Relative refr. capacity and discharge temp. increase: Reference refrigerants are those listed under "Substitute for", performance data are average values based on calorimeter tests.
(H): high temperature application
(M): medium temperature application
(L): low temperature application
Data is based on publications of various refrigerant manufacturers and is subject to change.

R22 and alternative refrigerants

R22

R502

R404A

R507A

R407A

R407F

R407H

R410A

R407C

R417A

R417B

R422A

R422D

R427A

R438A

R290

R1270

R717

R723

R744

R444B

R449C

R454C

Chemical

CHClF2

CH3CH2CH3

CH2CHCH3

NH3

NH3/ R-E170

CO2

Group

HCFC

CFC

HFC

HFC

HFC

HFC

HFC

HFC

HFC

HFC

HFC

HFC

HFC

HFC

HFC

HC

HC

NH3

NH3/ R-E170

CO2

HFO/HFC

HFO/ HFC

HFO/ HFC

Components

R22/ 115

R143a/ 125/ 134a

R143a/ 125

R32/ 125/ 134a

R32/ 125/ 134a

R32/ 125/ 134a

R32/ 125

R32/ 125/ 134a

R125/ 134a/ 600

R125/ 134a/ 600

R125/ 134a/ 600a

R125/ 134a/ 600a

R32/ 125/ 143a/ 134a

R32/ 125/ 134a/ 600/ 601a

R32/ 152a/ 1234ze(E)

R32/ 125/ 1234yf/ 134a

R32/ 1234yf

Name

chloro-difluoro-methane

propane

propylene / propene

ammonia

ammonia/ DME

carbon dioxide

L-20

XL20

Manufacturer

Honeywell

Chemours

Chemours

Substitute for

R502, R12

R502, R22

R502, R22

R22, R404A, R507A

R22, R404A, R507A

R22, R404A, R507A

R22, R13B1

R22, R404A, R507A

R22

R22

R22

R22

R22

R22

R404A, R507A, R22

R404A, R507A, R22

R404A, R507A, R22

R404A, R507A, R22

R23, R134a, R404A, R507A

R407C, R22

R407C, R22

R404A, R507A

Application max (°C)

12

10

0

0

0

0

0

12

12

12

0

0

0

0

0

12

12

12

12

20

12

12

12

Application min (°C)

-45

-50

-45

-45

-40

-40

-30

-25

-25

-25

-40

-40

-40

-40

-40

-40

-40

-20

-20

-20

-35

-35

-40

Appl. limitations max (°C)

7

7

7

7

7

7

7

7

7

7

Appl. limitations min (°C)

-35

-40

-30

-30

Appl. 2-stage max (°C)

-20

-30

-30

-30

-30

-40

-20

-20

-15

-15

-10

-25

Appl. 2-stage min (°C)

-50

-70

-70

-55

-55

-80

-55

-55

-50

-50

-50

-65

Oil 1

MO

AB

POE

POE

POE

POE

POE

POE

POE

POE

POE

POE

POE

POE

POE

PAO

PAO

MO

MO

POE

POE

POE

POE

Oil 2

AB

PVE

PVE

PVE

PVE

PVE

PVE

PVE

PVE

PVE

PVE

PVE

PVE

PVE

PAG

PAG

PAO

PAO

PAG

PVE

PVE

PVE

Oil 3

POE

POE

MO/HC

MO/HC

Oil with limitations 1

AB

AB

AB

AB

AB

AB

AB

AB

AB

AB

AB

AB

AB

AB

AB

AB

AB

Oil with limitations 2

MO

MO

Molar mass

86,47

111,64

97,6

98,86

90,11

82,06

79,1

72,59

86,2

106,75

113,12

113,6

109,94

90,44

99,13

44,1

42,08

17,03

22,77

44,01

72,76

90,78

Normal boiling point (°C)

-40,7

-45,4

-46,2

-46,7

-45,2

-46,1

-44,6

-51,4

-43,8

-39,1

-44,9

-46,5

-43,2

-43

-42,3

-42,1

-47,6

-33,4

-36,5

-78,3

-45

-44

-45,6

Normal dew point (°C)

-40,7

-45,4

-45,5

-46,7

-38,7

-39,7

-37,6

-51,4

-36,7

-34,1

-41,5

-44

-38,3

-36,2

-35,7

-42,1

-47,6

-33,4

-36,5

-78,3

-35

-38

-37,8

Temperature glide (K)

0

0

0,7

0

6,5

6,4

7

0

7,1

5

3,4

2,5

4,9

6,8

6,6

0

0

0

0

0

10

6

7,8

Crit. temp. (°C)

96

82

72

71

82

83

87

71

86

85

74

71

78

85

83

97

91

132

131

31

92

84

86

Crit. pressure (bar)

49,9

40,7

37,35

37,05

44,94

47,55

48,57

49,01

46,15

38,94

37,37

36,65

37,95

44,06

41,79

42,5

45,6

113

110

73,8

52,1

43,2

ODP

0,055

0,33

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

GWP AR4

1810

4657

3922

3985

2107

1825

1490

2088

1774

2346

2920

3143

2729

2138

2264

3

2

0

1

1

295

1251

148

GWP AR5

1760

4790

3940

3990

1920

1674

1380

1920

1620

2130

2740

2850

2470

2020

2060

3

2

0

1

1

295

1146

146

GWP AR6

1960

4728

4775

2262

1965

1615

2256

1908

0,02

1

166

Cond. temp. at 26 bar abs (°C)

63

60

56

54

59

57

60

43

61

67

58

55

62

63

63

70

61

60

58

-11

61

64

Cond. temp. at 40 bar abs (°C)

81

83

Relative refr. capacity (%)

80 (L)

105 (M)

107 (M)

98 (M)

104 (M)

99 (M)

140 (H)

100 (H)

97 (M)

95 (M)

100 (M)

90 (M)

90 (M)

88 (M)

86 (M)

104 (M)

100 (M)

105 (M)

Discharge temp. increase (K)

35

-34

-34

-19

-11

-8

-4

-8

-25

-37

-39

-36

-20

-27

4

12

60

35

Safety class

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A3

A3

B2L

B2

A1

A2L

A1

A2L

Pract. limit AEL (kg/m³)

0,3

0,45

0,52

0,53

0,33

0,32

0,38

0,44

0,31

0,15

0,069

0,29

0,26

0,29

0,079

0,008

0,008

0,00035

0,07

0,055

0,362

0,059