ECOLITE

Sound pressure levels

The measurements were taken with the refrigerant R134a at an operating frequency of 50 Hz.
Evaporation temperature to = -10°C, ambient emperature tamb = 32°C
The calculated averaged sound pressure level refers to free-field conditions at a distance of 10 m and cuboid reference surface.
The tolerance for all specifications is +/- 2 dB(A).
For the measured quantities and their units: Introduction

Sound pressure levels for ECOLITE condensing units. ECO Mode

Model

Sound pressure level in dB(A)

LHL3E/2EES-2

39.5

LHL3E/2DES-2

40.0

LHL3E/2CES-3

40.5

LHL5E/4FES-3

41.5

LHL5E/4EES-4

42.5

LHL5E/4DES-5

43.5

LHL5E/4CES-6

43.5