Application with Bitzer compressors

Motors for star-delta start (star-delta motors, Y/Δ motors) are used in some larger compressors, they are e.g.

Suitable Bitzer motors for star-delta start

For reciprocating compressors those motors may be suitable for star-delta start which are marked in the Technical Information KT-410 with motor code "..D" or "..S" and motor connection "∆" and "Y" (possibly in different lines). In addition, it should be noted whether the specified voltage ranges are available in the voltage network on site. If necessary, please consult Bitzer.

Example from KT-410 for compressors 2KES .. 4BES:
The 70S motor is suitable for star-delta start in voltage networks with 50 Hz and 400 V (3 phase).
The 40S motor is also suitable for star-delta start, but would need 230 V (3 phase) at 50 Hz, which is unusual e.g. in the EU.

Voltage range
(V)

Nominal voltage
(V)

Motor code

Motor connection

Nominal voltage
(V)

Voltage range
(V)

50 Hz

60 Hz

220-240

230

40S

∆

-

-

380-420

400

40S

Y

460

440-480

380-420

400

70S

∆

460

440-480

660-720

690

70S

Y

-

-

For screw compressors those motors are suitable for star-delta start which are marked in the Technical Information ST-410 with motor code "D" and motor connection "Y/∆".

Example from ST-410 for HS.95 compressors: The 40D motor is suitable for star-delta start.

Voltage range
(V)

Nominal voltage
(V)

Motor code

Motor connection

Nominal voltage
(V)

Voltage range
(V)

50 Hz

60 Hz

380-415

400

40D

Y/∆

460

440-480

For a given compressor, an adhesive label in the terminal box cover shows the possible starting modes. For star-delta start, the bridges for direct-on-line start may have to be removed.

Starting current for the design of star-delta start

The starting current shown in the Bitzer Software refers to the measured starting current when the rotor of the three phase motor is blocked (mean value of the currents in L1, L2 and L3, measured simultaneously after 4 s). This starting current (locked rotor) refers to the RMS value (root mean square value): To calculate it, the peak value of the corresponding alternating variable (here current) is divided by √2. The starting current in star (locked rotor) refers to the rated operating voltage in delta wiring. If the motor starts directly in star or delta wiring, these are the maximum starting currents to be expected. However, the first measured amplitude may be larger due to the high unbalances.

With star-delta start, the max. starting current can be reduced to up to approx. 66% of the delta starting current (rotor locked) in the BITZER SOFTWARE. However, this depends on the compressor in question. Furthermore, star phase and transition break must be optimally matched, the IEC connection must be used and start unloading must be correctly applied.

Information in the Bitzer Software

If a specific compressor is selected in the Bitzer Software, the available motors are displayed under "Power supply" - "Power voltage" according to the specified supply frequency (additional motors for North America (UL) under "60Hz UL"). The standard motor is preselected.

The selection corresponds to the specifications in the Technical Information on motor codes:

All further information concerning the motor can be found in the tab "Technical Data" under "Motor data":

Available motors and motor data for compact screw compressor CSH9573-240Y. "Starting current (Rotor locked)" indicates the measured current (root mean square, RMS) when the rotor is locked. This is the current for direct-on-line start in star wiring (650 A) or in delta wiring (2029 A) with a phase voltage of 400 V in this case. (The phase voltage for star-delta start always refers to the phase voltage in delta operation.)
Available motors and motor data for compact screw compressor CSH9573-240Y. "Starting current (Rotor locked)" indicates the measured current (root mean square, RMS) when the rotor is locked. This is the current for direct-on-line start in star wiring (650 A) or in delta wiring (2029 A) with a phase voltage of 400 V in this case. (The phase voltage for star-delta start always refers to the phase voltage in delta operation.)

Configuration star-delta start

For star-delta start, 3 contactors are required in the main circuit:

If the duration of the star phase and transition break is not controlled by the compressor module, it must be set correctly. In general, the following applies: Star-delta motor "Y/Δ"

With star-delta start, additional start unloading is usually required (Additional start unloading (SU)).

Measuring the real starting current for star-delta start and direct-on-line start in star wiring

The starting current of the compressor must not be measured at the cables between the switch cabinet and the compressor (outlined in red in the picture), because then the current via the star contactor is by mistake measured, too. To avoid this, the starting current should be measured directly at or before the compressor fuse (outlined in green in the picture):

The real starting current is best measured directly before the compressor fuse (here: F02), so that the current via the star contactor (during the start in star wiring) is not measured as well.
The real starting current is best measured directly before the compressor fuse (here: F02), so that the current via the star contactor (during the start in star wiring) is not measured as well.

Setting in the Best Software

When using the compressor modules CM-RC or CM-SW, the module controls the contactors for the desired starting mode and, if necessary, the start unloading. For details:

The starting mode can be set in the Best Software:

Choosing the starting mode in the Best Software, here with CM-SW-01.
Choosing the starting mode in the Best Software, here with CM-SW-01.

Arrangement of the wiring in the terminal box of the compressor

Risk of electric shock!
warning

Risk of electric shock!

Before performing any work in the terminal box: Switch off the main switch and secure it against being switched on again!

Close the terminal box before switching on again!

Make the connections correctly!

Make the connections correctly!

Reversed arrangement of the electrical connections leads to a short-circuit!

In the terminal box cover of Bitzer compressors, an adhesive label shows the possible starting modes and the respective connection of the mains phases to the motor pins. For a direct-on-line start, the cable bridges supplied may have to be mounted.

Arrangement of the wiring for reciprocating compressors:

Arrangement of the wiring for screw compressors:

Zoom
Motor connection for star-delta start CS. compressor (example)
Zoom
Motor connection for star-delta start HS.85 compressor (example)

The following figure shows the internal wiring in the motor:

Zoom
Schematic illustration of the internal wiring in the motor for star-delta start
Q02: main contactor (star-delta start) resp. compressor contactor (direct-on-line start)
Q03: delta contactor
Q04: star contactor
(1): bridges for direct-on-line start (optional accessories)

Schematic wiring diagrams

In the schematic wiring diagram a star-delta start is depicted like this, for example:

Star-delta start for an OS.85 screw compressorQ02: main contactorQ03: delta contactorQ04: star contactor M01: motor
Star-delta start for an OS.85 screw compressor
Q02: main contactor
Q03: delta contactor
Q04: star contactor
M01: motor

Schematic wiring diagrams for Bitzer compressors: