R410A and alternative refrigerants

The following table shows all available data for R410A and alternative refrigerants.

ODP: ozone depletion potential
GWP: global warming potential according to EN 378:2017; AR4: Fourth Assessment Report of the IPCC, AR5: Fifth Assessment Report of the IPCC
pract. limit AEL: assigned exposure limit according to EN 378:2017
Temperature glide: Total glide from bubble to dew line, based on 1.013 bar. Real glide depends on operating conditions.
Relative refr. capacity and discharge temp. increase: Reference refrigerants are those listed under "Substitute for", performance data are average values based on calorimeter tests.
(H): high temperature application
(M): medium temperature application
(L): low temperature application
Data is based on publications of various refrigerant manufacturers and is subject to change.

R410A and alternative refrigerants

R410A

R32

R452B

R454B

R463A

R466A

Refrigerant

R410A

R32

R452B

R454B

R463A

R466A

Chemical

CH2F2

Group

HFC

HFC

HFO/ HFC

HFO/ HFC

HFO/ HFC

HFO/ HFC

Components

R32/ 125

R32/ 125/ 1234yf

R32/ 1234yf

R32/ 125/ 1234yf/ 134a/ 744

R32/ 1234yf/ 13I1

Name

difluoro-methane

XL55, L-41y

XL41

XP41

N-41

Manufacturer

Chemours, Honeywell

Chemours

Chemours

Honeywell

Substitute for

R22, R13B1

R410A

R410A

R410A

R410A

R410A

Application max (°C)

12

15

15

15

15

15

Application min (°C)

-25

-15

-25

-25

-25

-25

Appl. limitations max (°C)

Appl. limitations min (°C)

-40

Appl. 2-stage max (°C)

-40

Appl. 2-stage min (°C)

-80

Oil 1

POE

POE

POE

POE

POE

POE

Oil 2

PVE

PVE

PVE

PVE

PVE

PVE

Oil with limitations 1

AB

AB

Oil with limitations 2

Molar mass

72,59

52,02

63,53

62,61

74,72

80,69

Normal boiling point (°C)

-51,4

-51,7

-50,7

-50,5

-59,9

-51,7

Normal dew point (°C)

-51,4

-51,7

-49,8

-49,5

-46,9

-51

Temperature glide (K)

0

0

0,9

1

13

0,7

Crit. temp. (°C)

71

78

77

78

76

76

Crit. pressure (bar)

49,01

57,8

52,2

52,67

52,44

51,44

ODP

0

0

0

0

0

0

GWP AR4

2088

675

698

466

1494

733

GWP AR5

1920

677

676

467

1377

696

Cond. temp. at 26 bar abs (°C)

43

42

46

47

47

46

Cond. temp. at 40 bar abs (°C)

61

65

66

65

65

Relative refr. capacity (%)

140 (H)

108 (H)

98 (H)

97 (H)

Safety group

A1

A2L

A2L

A2L

A1

A1

Pract. limit AEL (kg/m³)

0,44

0,061

0,062

0,061

0,299

0,099