R124 and alternative refrigerants

The following table shows all available data for R124 and alternative refrigerants.

ODP: ozone depletion potential
GWP: global warming potential according to EN 378:2017; AR4: Fourth Assessment Report of the IPCC, AR5: Fifth Assessment Report of the IPCC
pract. limit AEL: assigned exposure limit according to EN 378:2017
Temperature glide: Total glide from bubble to dew line, based on 1.013 bar. Real glide depends on operating conditions.
Relative refr. capacity and discharge temp. increase: Reference refrigerants are those listed under "Substitute for", performance data are average values based on calorimeter tests.
(H): high temperature application
(M): medium temperature application
(L): low temperature application
Data is based on publications of various refrigerant manufacturers and is subject to change.

R124 and alternative refrigerants

R124

R142b

R227ea

R236fa

R600a

R600

Refrigerant

R124

R142b

R227ea

R236fa

R600a

R600

Chemical

CHClFCF3

CClF2CH3

CF3CHFCF3

CF3CH2CF3

CH3CHCH3CH3

CH3CH2CH2CH3

Group

HCFC

HCFC

HFC

HFC

HC

HC

Name

chloro-tetrafluoro-ethane

1-chloro-1,1-difluoro-ethane

1,1,1,2,3,3,3-heptafluoro-propane

1,1,1,3,3,3-hexafluoro-propane

isobutane

butane

Substitute for

R114, R12B1

R114, R12B1

R12B1, R114

R114

R134a, R12

Application max (°C)

40

20

40

40

40

40

Application min (°C)

5

-10

-10

0

-10

0

Appl. limitations max (°C)

Appl. limitations min (°C)

-25

Oil 1

MO

MO

POE

POE

MO

MO

Oil 2

AB

AB

PVE

PVE

PAO

PAO

Oil 3

POE

POE

Oil with limitations 1

AB

AB

AB

AB

Oil with limitations 2

Molar mass

136,47

100,5

170,03

152,04

58,12

58,12

Normal boiling point (°C)

-12

-9,1

-16,3

-1,5

-11,8

-0,5

Normal dew point (°C)

-12

-9,1

-16,3

-1,5

-11,8

-0,5

Temperature glide (K)

0

0

0

0

0

0

Crit. temp. (°C)

122

137

102

125

135

152

Crit. pressure (bar)

36,2

40,6

29,3

32

36,3

38

ODP

0,022

0,065

0

0

0

0

GWP AR4

609

2310

3220

9810

3

4

GWP AR5

527

1980

3350

8060

3

3

Cond. temp. at 26 bar abs (°C)

105

112

96

115

115

129

Relative refr. capacity (%)

55 (H)

Discharge temp. increase (K)

-9

Safety group

A1

A2

A1

A1

A3

A3

Pract. limit AEL (kg/m³)

0,11

0,049

0,63

0,59

0,011

0,011