R123, R11
The following table shows the data for R123, R11 and alternative refrigerants.
ODP: ozone depletion potential
GWP: global warming potential according to EN 378:2017; AR4: Fourth Assessment Report of the IPCC, AR5: Fifth Assessment Report of the IPCC, AR6: Sixth Assessment Report of the IPCC
pract. limit AEL: assigned exposure limit according to EN 378:2017
Temperature glide: Total glide from bubble to dew line, based on 1.013 bar. Real glide depends on operating conditions.
Relative refr. capacity and discharge temp. increase: Reference refrigerants are those listed under "Substitute for", performance data are average values based on calorimeter tests.
(H): high temperature application
(M): medium temperature application
(L): low temperature application
Data is based on publications of various refrigerant manufacturers and is subject to change.
R123 | R11 | R245fa | R1224yd(Z) | R1233zd(E) | R1336mzz(E) | R600 | |
|---|---|---|---|---|---|---|---|
Chemical | CClF2CClFH | CCl3F | CF3CH2CF2H | (Z)-CF3-CF=CHCl | C3H2ClF3 | C4H2F6 | CH3CH2CH2CH3 |
Group | HCFC | CFC | HFC | HCFO | HCFO | HFO | HC |
Components | |||||||
Name | dichloro-trifluoro-ethane | trichloro-fluoro-methane | 1,1,1,3,3-pentafluoro-propane | (Z)-1-chloro-2,3,3,3-tetrafluoro-propene | trans-1-chloro-3,3,3-trifluoro-1-propene | trans-1,1,1,4,4,4-hexafluoro-2-butene | butane |
Manufacturer | Amolea | ||||||
Substitute for | R11 | R123 | R123, R11 | R123, R11 | R245fa | ||
Application max (°C) | 20 | 30 | 40 | 30 | 30 | 40 | 40 |
Application min (°C) | 0 | 0 | 5 | 0 | 0 | 0 | 0 |
Appl. limitations max (°C) | |||||||
Appl. limitations min (°C) | |||||||
Appl. 2-stage max (°C) | |||||||
Appl. 2-stage min (°C) | |||||||
Oil 1 | MO | MO | POE | POE | POE | POE | MO |
Oil 2 | AB | AB | special | PAO | |||
Oil 3 | POE | ||||||
Oil with limitations 1 | AB | ||||||
Oil with limitations 2 | |||||||
Molar mass | 152,92 | 137,37 | 134,05 | 133,5 | 164,06 | 58,12 | |
Normal boiling point (°C) | 27,8 | 23,8 | 15,1 | 14,6 | 18,3 | 7,6 | -0,5 |
Normal dew point (°C) | 27,8 | 23,8 | 15,1 | 14,6 | 18,3 | 7,6 | -0,5 |
Temperature glide (K) | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Crit. temp. (°C) | 184 | 198 | 154 | 156 | 166 | 130 | 152 |
Crit. pressure (bar) | 36,6 | 44,1 | 36,5 | 33,3 | 36,2 | 27,66 | 38 |
ODP | 0,02 | 1 | 0 | 0,00012 | 0,00034 | 0 | 0 |
GWP AR4 | 77 | 4750 | 1030 | 4 | 5 | 18 | 4 |
GWP AR5 | 79 | 4660 | 856 | 1 | 1 | 7 | 3 |
GWP AR6 | 90,4 | 5560 | 962 | 3,88 | 17,9 | 0,006 | |
Cond. temp. at 26 bar abs (°C) | 163 | 163 | 136 | 141 | 147 | 126 | 129 |
Cond. temp. at 40 bar abs (°C) | |||||||
Relative refr. capacity (%) | |||||||
Discharge temp. increase (K) | |||||||
Safety class | B1 | A1 | B1 | A1 | A1 | A1 | A3 |
Pract. limit AEL (kg/m³) | 0,1 | 0,3 | 0,19 | 0,048 | 0,011 |