R23, R13

The following table shows the data for R23, R13 and alternative refrigerants.

ODP: ozone depletion potential
GWP: global warming potential according to EN 378:2017; AR4: Fourth Assessment Report of the IPCC, AR5: Fifth Assessment Report of the IPCC, AR6: Sixth Assessment Report of the IPCC
pract. limit AEL: assigned exposure limit according to EN 378:2017
Temperature glide: Total glide from bubble to dew line, based on 1.013 bar. Real glide depends on operating conditions.
Relative refr. capacity and discharge temp. increase: Reference refrigerants are those listed under "Substitute for", performance data are average values based on calorimeter tests.
(H): high temperature application
(M): medium temperature application
(L): low temperature application
Data is based on publications of various refrigerant manufacturers and is subject to change.

R23, R13 and alternative refrigerants

R23

R13

R503

R508A

R508B

R744A

R170

R469A

R472A

R472B

R473A

Chemical

CHF3

CClF3

N2O

CH3CH3

Group

HFC

CFC

CFC

HFC

HFC

N2O

HC

HFC/ CO2

HFC/CO2

HFC/CO2

HFO/HFC

Components

R13/ 23

R23/ 116

R23/ 116

R744/ 32/ 125

R744/ 32/ 134a

R744/ 32/ 134a

R744/ 1132a/ 23/ 125

Name

trifluoro-methane

chloro-trifluoro-methane

nitrous oxide

ethane

WT69

Klea 473A

Manufacturer

TEGA

Angeletoni

Angeletoni

Orbia

Substitute for

R13, R503

R503

R503

R23, R508A, R508B

R23, R508A, R508B

R23

R23

R23

R23

Application max (°C)

-50

-30

-50

-50

-50

-40

-50

-40

-40

Application min (°C)

-95

-80

-90

-95

-95

-80

-95

-75

-80

Appl. limitations max (°C)

Appl. limitations min (°C)

Appl. 2-stage max (°C)

Appl. 2-stage min (°C)

Oil 1

POE

MO

AB

POE

POE

special

PAO

POE

POE

POE

POE

Oil 2

PVE

AB

MO

PVE

Oil 3

POE

Oil with limitations 1

AB

AB

Oil with limitations 2

Molar mass

70,01

104,46

87,24

100,1

95,39

44,01

30,07

59,1

50,39

54,8

52,58

Normal boiling point (°C)

-82

-81,4

-87,9

-87,6

-87,6

-88,5

-88,6

-78,5

-84,3

-82,9

-87,6

Normal dew point (°C)

-82

-81,4

-87,9

-87,6

-87,6

-88,5

-88,6

-61,5

-61,5

-54,8

-83

Temperature glide (K)

0

0

0

0

0

0

0

17

22,8

28,1

4,6

Crit. temp. (°C)

26

29

20

10

11

36

32

59

50,2

57,9

29,72

Crit. pressure (bar)

48,3

38,7

43,43

36,48

37,71

72,5

48,7

65,17

77,5

77,1

62,87

ODP

0

1

0,6

0

0

0,017

0

0

0

0

0

GWP AR4

14800

14400

14560

13210

13400

298

6

1358

353

526

1830

GWP AR5

12400

13900

13300

11600

11700

265

6

1250

329

484

1558

GWP AR6

16200

14600

273

0,437

1621

384

567

1835

Cond. temp. at 26 bar abs (°C)

2

11

-2

-3

-3

-7

4

23

-5

Cond. temp. at 40 bar abs (°C)

11

Relative refr. capacity (%)

Discharge temp. increase (K)

Safety class

A1

A1

A1

A1

A1

A1

A3

A1

A1

A1

A1

Pract. limit AEL (kg/m³)

0,68

0,5

0,35

0,23

0,25

0,0086

0,072

0,08

0,077