R134a
The following table shows the data for R134a and alternative refrigerants (R134a alternatives).
ODP: ozone depletion potential
GWP: global warming potential according to EN 378:2017; AR4: Fourth Assessment Report of the IPCC, AR5: Fifth Assessment Report of the IPCC, AR6: Sixth Assessment Report of the IPCC
pract. limit AEL: assigned exposure limit according to EN 378:2017
Temperature glide: Total glide from bubble to dew line, based on 1.013 bar. Real glide depends on operating conditions.
Relative refr. capacity and discharge temp. increase: Reference refrigerants are those listed under "Substitute for", performance data are average values based on calorimeter tests.
(H): high temperature application
(M): medium temperature application
(L): low temperature application
Data is based on publications of various refrigerant manufacturers and is subject to change.
R134a | R1234yf | R1234ze(E) | R513A | R450A | R600a | R444A | R456A | R471A | R516A | R152a | R474A | R475A | R476A | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Chemical | CF3CH2F | CF3FCH2 | C3H2F4 | CH3CHCH3CH3 | CHF2CH3 | |||||||||
Group | HFC | HFO | HFO | HFO/ HFC | HFO/ HFC | HC | HFO/ HFC | HFO/ HFC | HFO/ HFC | HFO/ HFC | HFC | HFO | HFO/HFC | HFO/HFC |
Components | R1234yf/ 134a | R1234ze(E)/ 134a | R32/ 152a/ 1234ze(E) | R32/ 1234ze(E)/ 134a | R1234ze(E)/ 1336mzz(E)/ 227ea | R1234yf/ 152a/ 134a | R1132(E)/ 1234yf | R134a/ 1234yf/ 1234ze(E) | R134a/ 1234ze(E)/ 1336mzz(E) | |||||
Name | 1,1,1,2-tetrafluoro-ethane | 2,3,3,3-tetrafluoro-1-propene | trans-1,3,3,3-tetrafluoro-1-propene | XP10 | N-13 | isobutane | AC5 | AC5X | ARM-42 | 1,1-difluoro-methane | ||||
Manufacturer | Chemours, Honeywell | Honeywell | Chemours | Honeywell | Koura (Mexichem) | Koura (Mexichem) | Honeywell | Arkema | Daikin | Gree | Honeywell | |||
Substitute for | R12, R22 | R134a | R134a | R134a, R12, R404A | R134a, R12 | R134a, R12 | R134a | R134a | (R134a) | R134a | R12, R22 | R134a | R134a | R134a |
Application max (°C) | 25 | 25 | 40 | 25 | 25 | 40 | 25 | 25 | 20 | 25 | 25 | 10 | 15 | 25 |
Application min (°C) | -20 | -25 | -10 | -25 | -25 | -10 | -20 | -25 | -20 | -25 | -20 | -35 | -30 | -15 |
Appl. limitations max (°C) | ||||||||||||||
Appl. limitations min (°C) | -30 | -30 | -30 | -25 | ||||||||||
Appl. 2-stage max (°C) | ||||||||||||||
Appl. 2-stage min (°C) | ||||||||||||||
Oil 1 | POE | POE | POE | POE | POE | MO | POE | POE | POE | POE | POE | POE | POE | POE |
Oil 2 | PVE | PVE | PVE | PVE | PVE | PAO | PVE | PVE | PVE | |||||
Oil 3 | POE | |||||||||||||
Oil with limitations 1 | AB | AB | AB | |||||||||||
Oil with limitations 2 | ||||||||||||||
Molar mass | 102,03 | 114,04 | 114,04 | 108,31 | 108,67 | 58,12 | 96,7 | 101,42 | 122,09 | 102,58 | 66,05 | 96,7 | 108,54 | 116,9 |
Normal boiling point (°C) | -26,1 | -29,5 | -19 | -29,6 | -23,4 | -11,8 | -35,7 | -30,8 | -16,9 | -29,4 | -24 | -43,1 | -28,8 | -19,1 |
Normal dew point (°C) | -26,1 | -29,5 | -19 | -29,5 | -22,8 | -11,8 | -24,6 | -25,4 | -13,7 | -29,4 | -24 | -36,4 | -28,3 | -16,1 |
Temperature glide (K) | 0 | 0 | 0 | 0,1 | 0,6 | 0 | 11,1 | 5,4 | 3,2 | 0 | 0 | 6,7 | 0,5 | 3 |
Crit. temp. (°C) | 101 | 95 | 109 | 95 | 104 | 135 | 106 | 103 | 112 | 97 | 113 | 87,1 | 99,3 | 110 |
Crit. pressure (bar) | 40,7 | 33,8 | 36,4 | 36,5 | 38,2 | 36,3 | 44,73 | 41,75 | 35,34 | 36,23 | 45,2 | 40,4 | 37,2 | 36,3 |
ODP | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
GWP AR4 | 1430 | 4 | 6 | 631 | 604 | 3 | 92 | 687 | 148 | 142 | 124 | 619 | ||
GWP AR5 | 1300 | 1 | 1 | 573 | 547 | 3 | 89 | 627 | 148 | 131 | 138 | 560 | 132 | |
GWP AR6 | 1530 | 0,501 | 1,37 | 673 | 643 | 148 | 153 | 164 | 2 | 659 | 156 | |||
Cond. temp. at 26 bar abs (°C) | 79 | 82 | 92 | 78 | 86 | 115 | 81 | 80 | 97 | 80 | 85 | |||
Cond. temp. at 40 bar abs (°C) | ||||||||||||||
Relative refr. capacity (%) | 97 (M) | 98 (M) | 75 (H) | 102 (M) | 88 (M) | 55 (H) | 67 (H) | |||||||
Discharge temp. increase (K) | -8 | -14 | -6 | -7 | -6 | -9 | -7 | |||||||
Safety class | A1 | A2L | A2L | A1 | A1 | A3 | A2L | A1 | A1 | A2L | A2 | A2L | A1 | A1 |
Pract. limit AEL (kg/m³) | 0,25 | 0,058 | 0,061 | 0,319 | 0,319 | 0,011 | 0,29 | 0,32 | 0,042 | 0,027 | 0,053 | 0,32 | 0,18 |