Closing the radial oil channel
This applies only to an OS.53, where a shaft seal without metal bellows is replaced by a version with a bellows.
The refrigeration compressor oil reaches the bearing surfaces differently for both shaft seal versions: in the new bellows design by means of a ring groove in the stationary unit and in the previous version without bellows by a radial oil channel in the bearing cover. When replacing, this oil channel must be closed.

- Insert grooved pin (Ø 4 x 10 mm) from the flange side into the oil channel in the bearing cover.
- Drive in the grooved pin by means of a hammer and a punch until it is level or a little below the sur face (see figure).
- Replace also sealing cover.