Removing the shaft seal with metal bellows

1 | stationary unit |
2 | sealing cover |
3 | stationary slinding ring |
4 | gasket ring |
6 | locating pin |
7 | oil drain pipe |
8 | oil drain hose |
9 | gasket of sealing cover |
10 | rotating unit |
11 | O-ring |
12 | set screw |
13 | slot for removal |
14 | drive pin |
15 | oil orifice |

- Loosen the fixing screws of the sealing cover (2) uniformly. Mind the spring tension of the shaft seal!
- Release the sealing cover with light taps of the plastic hammer if necessary.
- Remove the stationary unit (1). Depending on the model, two forcing threads in the sealing cover can be used.
- Remove gasket remains.
- The rotating unit (10) is secured radially to the shaft with three set screws (12). These are offset by 120° from one another. Now take the hexagon socket screw spanner with shortened leg from the spare shaft seal kit. Use this to loosen each set screw by at least one full turn.
NOTICE
Irreversible damage to the shaft is possible.
Irreversible damage to the shaft is possible.
When removing the shaft seal, the shaft may be damaged to such an extent that it can no longer be sealed. When removing the rotating unit:
- Loosen the set screws until they cannot touch the shaft.
- Do not tilt the rotating unit.
- Pull out the rotating unit with two hooks, using the slot for removal (13).
- With strongly sticking O-rings: use a pulling device.
If it is planed to reuse the rotating unit:
- When removing the rotating unit, hold it only by the slot for removal (13). Otherwise, the bellows may be overstretched or damaged.