Inspecting the shaft seal
A routine inspection of the shaft seal is not generally necessary. However, to ensure increased operational reliability, it is advisable to check in connection with an oil charge, in the event of faults in the oil supply, and at regular intervals when operating at high discharge gas and oil temperatures. Pay particular attention to cracks in the O-rings and to wear, scoring, material deposits, oil carbon and copper plating on the sealing rings. An oil leak rate of up to approx. 0.2 cm3/h is within the tolerance range. Any oil which does leak out can be led away by means of the pipe connection on the sealing cover of the shaft seal.
Possible failure causes
- Symptoms for lack of lubrication
- hardening and cracking on O-rings
- oil carbin
- scoring on the sliding face
- blocked filter of oil orifice
- too long time delay before oil solenoid valve opens, tolerance up to 2 s
- operation with too small pressure difference
- high refrigerant concentration in oil, oil temperature too low
- Cause for overheating
- same symptoms as for lack of lubrication
- oil injection temperature too high
- Cause for scores and wear on sliding rings
- high proportion of dirt in oil
- ause for copper plating
- high oil acidity
- Causes for strong vibrations
- irregular drive
- weak base frame
- coupling not sufficiently fixed
- coupling displaced