Whereas the electronic cooling unit valve group is mounted: activate the evacuation mode in the BEST SOFTWARE
WARNINGThe compressor is under pressure!

The compressor is under pressure!
Serious injuries are possible.
Depressurize the compressor!
Wear safety goggles!
NOTICE
Risk of damage to the motor and compressor!
Risk of damage to the motor and compressor!
Do not start the compressor while it is in a vacuum!
Do not apply any voltage, not even for testing!
Close shut-off valve after the cooling plate / cooling unit valve group
Activate evacuation mode in the BEST SOFTWARE
Whereas the evacuation mode is activated, the valves of the cooling unit valve group are being opened in order to evacuate the whole area of the cooling plate /cooling unit valve group.
- Bluetooth password: 8670
- It is recommended to promptly change this factory-set password in the BEST SOFTWARE.