Check cooling unit valve group / cooling plate for tightness, evacuate
- Check for tightness.
- Check the refrigerant circuit (assembly) for tightness, as a whole or in parts, according to EN378-2 (or other applicable equivalent safety standards). For this, create an excess pressure, preferably using dried nitrogen. Observe test pressures and safety reference:
DANGERRisk of bursting due to excessive pressure!

Risk of bursting due to excessive pressure!
The pressure applied during the test must never exceed the maximum permitted values!
Test pressure: 1.1-fold of the maximum allowable pressure (see name plate). Make a distinction between the high pressure and low pressure sides!
- Evacuate.
- Deactivate evacuation mode in BEST SOFTWARE.
- De-energize compressor and check if compressor is de-energized.
- Liquid line shut-of valve und shut-up valve after the evaporator pressure regulator öffnen.
Further information see operating instructions SB-160.