Oil filter
The inspection and replacement intervals of all filters depend upon the contamination level of the whole system.
Inspection interval | Replacement interval |
|---|---|
5000 h, at least once a year | after first 50 h ... 100 h |
HS.53 .. HS.74, HS.95 and OS.53, OS.74, OS.95
If the pressure drop increases above 0.5 bar at the filter with stabilisized operating conditions the filter cartridge has to be changed. Oil the alu gaskets for the connection adaptor. Screw in the filter cartridge until tight and then release it by a quarter of a turn.
HS.85 and OS.85
The oil filter's pollution degree is monitored permanently during operation. If the signal lamp of oil filter monitoring (F10) lights up, check oil filter for pollution and replace if necessary.
See also
- SB-110: Operating instructions Semi-hermetic screw compressors HS.53 .. 95
- SB-510: Operating instructions Open drive screw compressors OS.85
- SB-520: Operating instructions Open drive screw compressors OS.85, OS.95, OS.105
- SW-111: Video mounting instructions: OS.85 / HS.85: Replacing the oil filter
.