Oils for refrigerant R22
BITZER compact screw compressors for R22 are charged with a high-quality complex ester oil. It significantly exceeds the requirements of DIN 51503, Part 1, for refrigeration compressor oils with respect to water content and total acid number (TAN). It mixes well with R22 and is therefore especially suitable for operation with this substance.
Charakterisation and application range
B320SH | |
|---|---|
oil type | complex ester |
Designation on compressor | – – |
application range | |
condensing temperature | CSH: .. 60 °C |
evaporation temperature | +12,5 .. -15 °C |
discharge gas temperature | 60 .. max. 120 °C |
Material safety data sheets
Apart from this document, please observe the material safety data sheet (MSDS) for the respective oil. It contains information on toxicity, handling, personal protective equipment and disposal of the oil. Material safety data sheets for all Bitzer oils are available on request.
Technical data
Oil | Type | Flash-point (°C) | Pour point (°C) | Density (g/ml) | Kinematic viscosity (cSt) | Specific heat capacity (kJ/kg*K) | Thermal conductivity (W/m*K) | ||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
at -30°C | at 15°C | at 100°C | at 20°C | at 40°C | at 100°C | at 40°C | at 100°C | at 40°C | at 100°C | ||||
B320SH/ B320SX | complex ester | 258 | -42 | 1.052 | 1.016 | 0.958 | 993 | 310 | 32 | 1.68 | 1.85 | 0.12 | 0.12 |
Miscibility gaps B320SH
M: Range of complete miscibility.
P: Phase separation range (miscibility gap).
Refrigerant solubility in B320SH
The following diagram can be used to read off the refrigerant content in the lubricant depending on refrigerant pressure and oil temperature.
Warning values for used oil
B320SH is categorized as group KC according to DIN51503-1. To determine the used condition of the oil, e.g. with respect to water content or total acid number (TAN), the reference values of DIN 51503-2, apply.
Warning values B320SH | |
|---|---|
Kinematic viscosity at 40°C (DIN EN ISO3104) | outside of 264 .. 356 cSt |
Max. water content | 150 mg H2O/kg oil |
Total acid number | 0,2 mg KOH/g |
Elastomer compatibility
Relevant literature recommends ethylene propylene diene rubber as seaI material for complex ester with refrigerant R22.