Variant: refrigerant cooled external oil coolers (thermosiphon oil cooling)

Thermosiphon oil cooling is based on the principle of gravity circulation of refrigerant on the high pressure side. Features:

For oil cooling, refrigerant is branched off from the accumulator and fed directly into the lower oil cooler. In counterflow to the hot oil, part of the liquid refrigerant evaporates under heat absorption. As a two-phase mixture, it flows back to the condenser inlet either directly or via the accumulator. (In the design with accumulator, the liquid part is separated). The evaporated part is then liquefied again in the condenser when mixed with the discharge gas flow.

To ensure gravity circulation, the liquid line to the oil cooler must have a certain height difference: A defined excess pressure can be achieved through the liquid column, which must be higher than the sum of the pressure losses in the pipes, oil cooler and condenser. If necessary, a refrigerant pump or injector can be used to support circulation.

A modulating oil mixing valve controls the oil temperature. An alternative is the regulated refrigerant supply to the oil cooler.

The following illustrations show examples of design variants of thermosiphon circuits. Each system must be calculated and designed individually. Data is available in the Bitzer Software and the Technical Information ST-500. Detailed calculation documents are available on request.