Put condensing unit into operation again

- Evacuate compressor.
- Open compressor valves again.
- Check tightness.
DANGERRisk of bursting due to excessive pressure!

Risk of bursting due to excessive pressure!
The pressure applied during the test must never exceed the maximum permitted values!
Test pressure: 1.1-fold of the maximum allowable pressure (see name plate). Make a distinction between the high-pressure and low-pressure sides!
Turn on main switch
- Check functioning and tightness again during operation.
Attach and mount front door again
Close front door
- Condensing unit key