Replacing the solenoid valve
Step 1: Remove solenoid coil with electric connector of the device from armature
Step 2: Remove solenoid valve
- Ratchet wrench with TX50 socket wrench
Step 3: Remove old gasket and spring
Schritt 4: Clean sealing face
- Cleaning agent and rags
Step 5: Position new gasket and spring
Step 6: Mount solenoid valve and cable bracket with new screws
- Ratchet wrench with TX50 socket wrench
- Torque spanner
- Tightening torque: 70 Nm
Schritt 7: Place solenoid coil onto armature and tighten with nut and washer
- Spanner SW 14
- Torque spanner
- Tightening torque: 5 Nm
After that:
- Check the function of the solenoid valves
- If the error persists, please contact BITZER. The cylinder head may have to be replaced.