Introduction
The CM-RC-01 compressor module integrates the entire electronic periphery of the compressor.
The CM-RC-01 monitors the main operating parameters of the reciprocating compressor: The notor and discharge gas temperature, oil supply and application limits. It protects the compressor from operating under critical conditions. The module switches the oil heating on and off and, depending on compressor series and individual equipment, the start unloading, the compressor cooling and the capacity regulators according to the performance requirements of a superior system controller. It supplies power to the associated components. The module also switches the motor contactors on and off during start. Additional time relays are not required. The high pressure switch can be connected directly to the compressor module.
During operation, numerous operating data of the compressor can be tracked using the best software, for example the operating point in the application limits diagram. These data are recorded and allow the system operation to be diagnosed. Four coloured LEDs indicate the operating condition of the compressor module.
This technical information describes the CM-RC-01 with the compressors 8FTE-100K .. 8CTE-140K and 8FTE-100Z .. 8CTE-140Z: The operating and monitoring functions, possible electrical connections, the state of delivery, the commissioning of the compressor module including the supplied peripheral devices and the communication with the Best software. For detailed information on Modbus programming and other technical data, see the Best software. All compressors of this series are factory-equipped with a CM-RC-01.