Inputs and outputs for peripheral devices
Terminal strip CN4 | |
Voltage supply of oil heater (E01) | 115 .. 230 V +10%/-15%, 50/60 Hz, max. 2 A Use only oil heaters released for the respective compressor, see Technical Information KT-150. Connection suitable for oil heater with maximum power consumption: 300 W at 230 V and 150 W at 115 V |
Terminal strip CN5 | |
Voltage supply of the solenoid valve for oil return by OLM-IQ (M41) | Voltage output corresponds to the selected operating voltage. Use only original spare parts! |
Terminal strip CN6 | |
Voltage supply of the solenoid valves for capacity control (M11 to M14) | Voltage output corresponds to the selected operating voltage. All solenoid valves are included in the compressor’s scope of delivery. Use only original spare parts! |
Terminal strip CN11, terminal 1 | |
Input for start signal from the superior controller (K01) or for auxiliary relay for message from FI (K19) | 24 V DC from internal source |
Terminal strip CN12 | |
Connection for pressure transmitters | The pressures are measured independently of the ambient pressure. An altitude correction is not necessary. |
Terminal strip CN13 | |
Analogue signal for capacity control | 0 .. 10 V DC, accuracy ±2% at full scale with max. 1 mA or control performance: ±0.5% at 100% linear control signal required This type of control is particularly suitable for systems with simple controllers equipped with an output for 0 to 10 V and with a relay and when the CN14 terminal strip is used for the best software. |
Terminal strip CN14 | |
Modbus connection | Modbus RTU, RS485, detailed description see best software. |