Monitored functions
Monitored function | Delay time after compressor start | Warning | Critical alarm | Fault |
|---|---|---|---|---|
Discharge gas temperature | --- | > 135°C | --- | > 150°C CM-RC-01 switches off immediately. |
Motor temperature | --- | --- | --- | CM-RC-01 locks out immediately. |
Oil supply | --- | 1 s | --- | CM-RC-01 locks out after further 85 s. |
Oil supply | --- | 5 s | --- | CM-RC-01 locks out after further 90 s. |
Oil supply | --- | 5 s | --- | CM-RC-01 switches off after further 25 s. |
Switching frequency of the compressor | --- | depending on compressor model, see respective operating instructions | --- | --- |
Application limits, option | 120 s | < 2 K within the application limit | > 2 K outside the application limit CM-RC-01 switches off after 30 s. | > 4 K outside the application limit CM-RC-01 switches off immediately. |
Low pressure, option | --- | --- | --- | < entered value |
High pressure, option | --- | --- | --- | > entered value |