Introduction
The CM-RC-01 compressor module integrates the entire electronic periphery of the compressor.
The CM-RC-01 monitors the main operating parameters of the reciprocating compressor: The notor and discharge gas temperature, oil supply and application limits. It protects the compressor from operating under critical conditions. The module switches the oil heating on and off and, depending on compressor series and individual equipment, the start unloading, the compressor cooling and the capacity regulators according to the performance requirements of a superior system controller. It supplies power to the associated components. The module also switches the motor contactors on and off during start. Additional time relays are not required. The high pressure switch can be connected directly to the compressor module.
During operation, numerous operating data of the compressor can be tracked using the best software, for example the operating point in the application limits diagram. These data are recorded and allow the system operation to be diagnosed. Four coloured LEDs indicate the operating condition of the compressor module.
The compressor module can be delivered pre-installed in these reciprocating compressors in a wide variety of equipment variants:
- Compressors for standard refrigerants: 4FES-3(Y) .. 8FE-70(Y)
- Compressors for high temperature heat pumps and transport applications: 4FESH-3Y .. 6FEH-50Y
- Compressors for subcritical R744 applications with high standstill pressures: 4FME-7K .. 6PME-40K and 4FME-7Z .. 6PME-40Z
- Compressors for transcritical R744 applications: 4PTE-6K .. 8CTE-140K and 4PTE-6Z .. 8CTE-140Z
- ECOLINE+ for transcritical R744 applications: 4PTEU-6LK .. 6CTEU-50LK and 4PTEU-6LZ .. 6CTEU-50LZ
The CM-RC-01 can be easily retrofitted to the first two compressor groups.
This technical information describes the CM-RC-01: The operating and monitoring functions, possible electrical connections, the state of delivery, the commissioning of the compressor module including the supplied peripheral devices and the communication with the BEST software. The retrofitting of components can be found in specific maintenance instructions for the respective compressor series. For detailed information on Modbus programming and other technical data, see the Best software.
The operation of compressors 8FTE-100K .. 8CTE-140K and 8FTE-100Z .. 8CTE-140Z with CM-RC-01 is described in Technical Information KT-231.