High pressure switch (B10)

According to EN378, each compressor must be provided with a high pressure switch (B10) for safety cut-out in the safety chain. Depending on the displacement and refrigerant charge, it must be designed as a safety pressure cut-out and / or only as pressure cut-out. The software-controlled monitoring of the compressor module via the high pressure transmitter (B50) does not sufficiently ensure the safety cut-out function. The high pressure switch (B10) should preferably be connected to terminal strip CN3. The data are analysed and logged in this case.

The installation of a low pressure switch is not necessary, depending on local regulations. The compressor module is provided with an automatic low pressure cut-out function. This option can be activated if a low pressure transmitter (B51) is installed, Activating high and low pressure switches.