Screwed nipples: Sensor and prism units

Size

Component

1/8-27 NPTF

Schrader valve

20 .. 25 Nm

1/4-18 NPTF

Schrader valve

30 .. 35 Nm

1/8-27 NPTF

temperature sensor

30 Nm

3/8-24 UNF

pressure transmitter max. 160 bar

26 .. 28 Nm

7/16-20 UNF

oil connection at OLM-IQ-AS

13 Nm

7/16-20 UNF

pressure transmitter

15 Nm

1/2-20 UNF

pressure transmitter max. 100 bar

26 .. 28 Nm

G1/4

pressure transmitter

35 Nm

M20 x 1.5

DP-1

50 .. 60 Nm

M20 x 1.5

Delta-PII, OLC-K1, OLC-D1

75 Nm

Schrader valve covers

Screwing cap of straight Schrader valves 7/16-20 UNF: 5 .. 10 Nm

Union nut der T-Schrader valves 3/4-16 UNF: 15 Nm

Oil monitoring Delta-PII, OLC-K1, OLC-D1 and DP-1

Screwing cap of electronic or opto-electronic unit: max. 10 Nm

Pressure transmitter

  1. Remove Schrader insert and spacer pieces.
  2. Then screw on the screwing cap.

Tightening torques of all NPTF screwed nipples not mentioned here Plugs without gasket.