Sealing screws with fine thread, plugs and screwed nipples
These screwed connections may be equipped with copper (Cu), aluminium (Al) gasket or O-ring.
Size | Cu | Al | O-ring |
|---|---|---|---|
M10 x 1 | 25 Nm | 30 Nm | |
M14 x 1 | 50 Nm | ||
M18 x 1.5 | 60 Nm | ||
M20 x 1.5 | 80 Nm | 70 Nm | 20 Nm |
M22 x 1.5 | 100 Nm | 80 Nm | 30 Nm |
M24 x 1.5 | 100 Nm | 90 Nm | |
M26 x 1.5 | 150 Nm | 110 Nm | 40 Nm |
M30 x 1.5 | 120 Nm | 120 Nm | |
M48 x 1.5 | 300 Nm | ||
M52 x 1.5 | 100 Nm | ||
G1/4 | 40 Nm | ||
G1 1/4 | 180 Nm | ||
1 1/8-18 UNEF | 50 Nm |
The listed tightening torques apply to all other metric screwed nipples.
The listed tightening torques apply to oil drain plugs. Possible sizes: M20x1.5, M22x1.5 or M26x1.5.