The OLM-IQ
The OLM-IQ is an oil level controller with optimised logic. It is an option for most compressors equipped with CM-RC-01. It can be installed in addition or as an alternative to oil monitoring.
The OLM-IQ itself consists of the OLM-IQ-AS actuator sensor unit (B43 and M41) and the logic in the CM-RC-01 to which the unit is connected. This unit consists of two components: The oil level sensor (B43), which is mounted in the compressor in place of the sight glass, and an integrated solenoid valve (M41). The measured data from the actuator sensor unit are evaluated by the CM-RC-01. The compressor module switches the OLM solenoid valve. This oil level control remains active even during compressor standstill.
The oil level sensor in the sight glass works with a float that provides a continuous signal. This measurement is independent of optical sources of error such as oblique incidence of light and and also determine the oil level very reliably in the case of oil foam.
The oil connection must be permanently supplied with bubble-free oil. This is a prerequisite for the OLM-IQ to function properly.